A three phase circuit breaker is rated at 2000 MVA, 33 kV. The symmetrical breaking current is: 

This question was previously asked in
NMDC Junior Officer Electrical 24 April 2022 Official Paper
View all NMDC Junior Officer Papers >
  1. 20 kA
  2. 60 kA
  3. 80 kA
  4. 35 kA

Answer (Detailed Solution Below)

Option 4 : 35 kA
Free
NMDC Junior Officer ME: Strength of Material Mock Test
1 K Users
20 Questions 20 Marks 24 Mins

Detailed Solution

Download Solution PDF

Breaking capacity of a circuit breaker

The rated breaking capacity is defined as the maximum fault current a circuit breaker can successfully interrupt without being damaged.

It is always expressed in KVA and the current corresponding to breaking capacity is known as the breaking current.

The breaking current is given by:

\(I_b={MVA\over \sqrt{3}\times V_{L}}\)

where, Ib = Breaking current

MVA = Breaking capacity

VL = Line-to-line voltage

The relationship between making and breaking current is:

\(I_m=2.55\times I_b\)

where, Im = Making current

Ib = Breaking current

Calculation

Given, Breaking capacity = 2000 MVA

VL = 33 kV

\(I_b={2000\space \times 10^6\over \sqrt{3}\times 33\times 10^3}\)

Ib = 34.9 kA (OR) 35 kA

Latest NMDC Junior Officer Updates

Last updated on Nov 29, 2024

-> The CBT for the NMDC Junior Officer Recruitment, scheduled on 4th December 2024 has been postponed until further notice.

-> The NMDC Junior Officer Notification 2024 has been released for 153 vacancies.

-> The selection of candidates is based on a Computer Based Test and Skill Test.

-> Depending on the posts, Diploma-holders, Graduates, and Postgraduates can apply for this post.

Get Free Access Now
Hot Links: teen patti gold apk download teen patti 50 bonus teen patti master app real teen patti